Description

The SINAF 2.0 active filter is equipment designed to solve the faults which may occur in a three or four wires, three phase installation. It includes the following functions:
• Harmonic filtering.
• Phase current balance.
• Power factor correction.
This is the ideal solution for installations with a large amount of single-phase and three-phase loads generating harmonics such as computers, UPC, lights a lifting equipment.

The SINAF 2.0 filter allows the selective removal of harmonics using the configuration of its DSP controls. SINAF corrects both the existing third harmonic component in neutral and the unbalanced current itself at 50 Hz achieving practically neutral currents (3 phases/4 wires).

Connecting the SINAF 2.0 filter must be in parallel with the loads to be corrected. The filter can operate in three wire systems (with or without neutral).

The correction capacity of the SINAF 2.0 is expressed as the RMS current value. The available capacity may be used for any three functions: filtering, balancing or correcting reactive. The SINAF has two different correction capacities:
• RMS current which the equipment is capable of injecting
into phase conductors
• RMS current which the equipment is capable of injecting into the neutral conductor, regardless of the phase.
The available correction capacity in the conductor is 1.5 times the phase capacity. This allows systems with high third harmonic content to be corrected.

Weight Dimensions Part Number
(kg) (WxHxD)mm  
3Wires
135 500x830x450 SINAF340025
212 650x1350x450 SINAF340050
272 660x1470x550 SINAF340100 
505 1190x1900x720 SINAF340150
511 1190x1900x720 SINAF340200
4Wires
135 500x830x450 SINAF440025
212 650x1350x450 SINAF440050
272 660x1470x550 SINAF440100 
505 1190x1900x720 SINAF440150
511 1190x1900x720 SINAF440200
SINAF340200 SINAF340150 SINAF340100 SINAF340050 SINAF340025  
SINAF440200 SINAF440150 SINAF440100 SINAF440050 SINAF440025  
200 A RMS 150 A RMS 100 A RMS 50 A RMS 25 A RMS Harmonic phase current
600 A RMS 450 A RMS 300 A RMS 150 A RMS 75 A RMS Harmonic neutral current
400 A PICO 300 A PICO 200 A PICO 100 A PICO 50 A PICO Harmonic peak current
Electrical characteristics
230-400-440-480V ± 15%  (3W) / 400 V  ± 15% (4W) Nominal Voltage
50 Hz / 60 Hz  +/- 10% Frequency
3 phases with or without neutral wire Number of phases
Filter specifications
2nd to 50th harmonic Current harmonics compensation
3rd to 25th harmonic Specified harmonic selection
≥ 85% Filtering efficiency
Yes Load current balancing
Yes, up to ≥ 0.98 PF Reactive current compensation
Digital, DSP Controller
< 1ms Transient Response Time
< 65 dB Noise level
Protection from over current by current limitation at filter nominal value Current limitation
Color LCD TFT 7” Graphic Display Panel
≤ 8% of rated current Heat losses
Standards
EN61000-3-4 Reference Harmonic Standard
IEEE519-1992  
EN60146 Reference Design Standard
EN50178 Safety Standard
EN55011 Electromagnetic Compatibility
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-6-2
EN61000-6-3
Display functions
Start, stop, reset alarm and filter status description Controls
Configuration of all filter parameters including: harmonics filtering, load balancing, reactive compensation, load transformer ratio, minimum current, control algorithm and number off SINAF 2.0 in parallel. Setup

Voltages and currents measurements. Real, reactive and apparent power and power factor measurements. Current harmonics and harmonic spectrum graph.

Electrical values display
Environmental conditions
 +0ºC … +50ºC Operating Temperature
0% … 90% without condensation Relative humidity
< 2000m Operating Alititude
IP31 Protection degree
Forced air cooled Ventilation