Description

PFCL Elite controller has a built in power analyzer allowing the measurement of main electrical parameters (voltage, current, harmonics, active and reactive power, apparent power, etc.). The device gives a detailed information on both, voltage and current harmonic components. PFCL Elite controller measures also ambient temperature and keeps a record of maximum and minimum values of all measured parameters.

Built-in leakage control

PFCL Elite have a built-in circuit to measure the earth leakage current through a WGC transformer. The regulator is able to measure the individual leakage of each capacitor. This allows to disable a damaged capacitor if an excess of leakage current is detected without interrupting the supply service.

Plug and Play

A series of parameters must be configured when a power factor regulator is installed, to make sure that it operates correctly. Some of these parameters might be hard to know, such as, for example, the voltage phases or the voltage corresponding to the current measured, as well as the current transformer ratio. PFCL Elite has been designed with a smart automatic process that detects the necessary parameters, such as:

• C/K: calculates the ratio of the current transformer and the power of the smallest step.
• Phase: Identifies the voltage sequence and correspondence with current. In other words, it identifies the UL1, UL2, UL3, when the current measured is IL1, IL2, IL3 and whether it is connected in the opposite way or not.
• Number of stages installed and Program: the system connects all stages in a sequence, finds out how many stages are installed and then calculates the program, i.e., the power ratio of the capacitors.

Serial Communications

PFCL Elite controllers are equipped with RS-485 communication with MODBUS protocol. This allows the integration of the PF regulator in a data network driven by a computer (PC). Enables data recording, remote control, supervision and preventive maintenance of the PF correction equipment itself and of the whole LV network.

AUTO-ON-OFF Function

This function allows to define the operating mode of each individual capacitor step:

• Automatic mode (Auto).
• Fixed mode (ON): Capacitor is always ON.
• Disconnected mode (OFF). Capacitor is always OFF.

Safety and maintenance

• PFCL Elite performs a capacitor test every time that a capacitor step is switched ON. The real power and the leakage current of each step can be displayed.
• Up to 14 different alarm conditions can be programmed.
• Internal counter register which counts the number of operations of each individual capacitor step

Steps Size (mm) Power (V) Model Code
144 x 144 230 PFCL Elite 6 PFCL06230
144 x 144 400 PFCL Elite 6 PFCL06400
12 144 x 144 230 PFCL Elite 12 PFCL12230
12 144 x 144 400 PFCL Elite 12 PFCL12400
6 144 x 144 110 PFCL Elite 6 PFCL06110
Technical characteristics
400, 230, or 110 V a.c. +15 % -10 %;  50 / 60 Hz,  (see label) / Power supply: UL1- UL2. Measurement UL1, UL2, UL3 and UN Main power supply and voltage measurement
Section  1,5 mm2 , gl 0.5 to 2 A protection fuse  Power supply cables 
Current transformer (CT), In /5 A AC., / preferably on phase L1. Min. cable section. 2.5 mm2 Current measurement circuit
Nominal current of transformer secondary: I∆sec = 2 mA AC. / Transformer with ratio of 500: I∆ = 1 A AC. +20% Leakage current measurement circuit
Current I: 0.05  … 5 A AC (maximum overload +20%) / Leakage current I∆: 0.01 … 1 A AC(maximum overload +20%) Current measurement margin
Voltage and current: 1 %;   cos φ :   2 % ±  1 digit Measurement accuracy
External temperature approximation. Range: 0 … 80ºC. Accuracy: ±  3 ºC Temperature measurement
8.2 VA (empty); 9.3 VA (6 relays); 11 VA (12 relays) Consumption
Relays. Contacts for Umax. 250 Vac., 4 A AC., AC1.  Output
Cable section 1.5 mm2, / protection with circuit breaker (C curve) of 6 A or gl 6 A fuse Cabling and output relay protection
Switched relay for use exclusively for the alarms Alarm relay
IEC 62053-23 (2003-01) Ed. 1.0 Standards
IEC 61326-1  
EN61010-1  
UL 508  
Category III,  Class II , according to  EN 61010-1 Safety/Insulation
IP40 (equipment mounted, cabinet front panel) Protection degree 
IP30 (equipment not mounted) according to EN-60529  
Temperature: -20 … +60ºC;  Relative humidity: max. 95% (without condensation). Max. altitude: 2000 m Admissible environmental conditions
FCP (a program that minimises the number of operations) Control system 
Interface: RS485. Protocol: MODBUS. Speed: 9600, 19200, 38400 Communications
PFCL Elite controller measures and operates in 4 quadrants according to the attached diagram