General characteristics

· The MCAplus network analyser is an electronic device that allows the reading of the 48 main parameters of a supply network in the true RMS values.

· It is specially designed for its easy installation and set up, it requires the connection of four voltage terminals and three current transformers. The four frontal buttons allow to change the displayed parameters in a few seconds. The MCAplus have LCD display for an easy reading in all light conditions.

· MCAplus is also available in advanced version with communication module and optional software.

L3 L2 L1 III   Parameter
  V Simple voltage     phase-phase
  V Compound voltage     phase-neutral
A Current
kW Activa power
  kvar Reactiva power
    Power factor
        Cos φ
    THD (U) %
    THD (I) %
    d (U) %
    d (I) %
kvar C Capacitive reactive power
kvar L Inductive reactive power
      kVa Apparent power
      Hz Frequency
      kWh Active energy
      kvarh C Capacitive reactive energy
      kvarh L Inductive reactive energy
      kVAh Apparent energy
      kW Active power maximeter
      kVA Apparent power maximeter
  A Current maximeter
A Neutral current
Technical characteristics
Power supply
230 V ac   Single phase
-15 % / +10 %  Voltage tolerance
50 – 60 Hz Frequency
4,2 VA Max. consumption
-10º C  +  50 º C Operating temperature
5% ~ 95% Humidity (wihtout condensation)
Mechanical characteristics
Self extinguishing V0 plastic Box material
Protection
IP  54 Equipment assembly (front)
IP  31 Non assembled equipment (side and rear cover)
96 x 96 x 63 Dimensions (mm)
0,400  kg  Weight
Accuracy class
0,5 %  ±  2 digits Voltage
0,5 %  ±  2 digits Current
1 %  ±  2 digits Powers
Measurement conditions
+ 5 ºC   + 45 ºC Temperature
0,5 … 1 Power factor
10….. 100 % Measurament margin (scale range)/(Current transformar not include)
Measurement circuit
Max. 300 Nominal voltage phase-neutral
Max. 520 V ac Between phase
45 ~ 65 Hz  Frequency
In / 5 A Nominal current
1,1 In Permanent overload
 0,75 VA Current circuit consumption
Advanced version
Transistor output features
NPN Type: Opto.isolated transistor (open collector)
24  V dc Maximun operating voltage
50 mA Maximun operating current
5 pulses/sec. Maximun frequency
100 ms Lenght of pulse
RS 485 Communication
Cat. III – 300 V ca / 520 ca   EN-61010      Safety
Class II double insulation against electric shock
IEC 348 Standards
IEC 571-1
IEC 664
IEC 801
EN 61000-6-1
EN 61000-6-3
EN-61010-1
VDE 0110
UL 94
Voltage (V) Communication Module Size (mm) Model Code
230  No  96 x 96 MCA plus standard MCAP03230
230 YES  96 x 96 MCA plus advanced MCAP04230
Power Control software AMCASOFT00
Connectors included. Cables not included. Converter /  RS485/RS232 AMCARS485232I