General characteristics

· The MCA Plus II network analyser is an electronic device that allows the reading of the main advanced parameters of a supply network in the true RMS values.

· It is specially designed for its easy installation and set up, it requires the connection of four voltage terminals and three current transformers. The capacitive control keypad in the front allows to change the displayed parameters in a few seconds. The MCA Plus II have LCD backlight display for an easy reading in all light conditions.

New features

● Suitable for MV and LV installations
● 4-Quadrant measurement for consumption and generation in the same measurement point
● High IP protection (Frontal IP65)
● 2 built-in digital outputs (S0 Interface or alarms)
● 2 built-in digital outputs by relay
● 2 built-in digital inputs (tariff selection or external alarms)
● RS-485 Modbus/RTU Communications
● Backlight touch keyboard
● Analog visualizations for instantaneous parameters (Power, Max Power reach and Cos φ or PF)
● Backlight display
● LED Alarm indicator

L3 L2 L1 III   Parameter
  V Simple voltage phase-phase
  V Compound voltage phase-neutral
A Current
kW Activa power
  kvar Reactiva power
    Power factor
        Cos φ
    THD (U) %
    THD (I) %
    d (U) %
    d (I) %
kvar C Capacitive reactive power
kvar L Inductive reactive power
      kVA Apparent power
      Hz Frequency
      kWh Active energy
      kvarh C Capacitive reactive energy
      kvarh L Inductive reactive energy
      kVAh Apparent energy
      kW Active power maximeter
      kVA Apparent power maximeter
  A Current maximeter
A Neutral current
Power supply
85 … 265 Vac / 95 … 300 Vcc  Single phase
-15 % / +10 %  Voltage tolerance
50 – 60 Hz Frequency
4,2 VA Max. consumption
-10º C  +  50 º C Operating temperature
5% ~ 95% Humidity (wihtout condensation)
Mechanical characteristics
Self extinguishing V0 plastic Box material
Protection
IP  54 Equipment assembly (front)
IP  31 Non assembled equipment (side and rear cover)
96 x 96 x 63 Dimensions (mm)
0,400  kg  Weight
Accuracy class
0,5 %  ±  2 digits Voltage
0,5 %  ±  2 digits Current
1 %  ±  2 digits Powers
Measurement conditions
+ 5 ºC   + 45 ºC Temperature
0,5 … 1 Power factor
10….. 100 % Measurament margin (scale range)
(Current transformar not include)
Measurement circuit
Max. 300 Nominal voltage phase-neutral
Max. 520 V ac Between phase
45 ~ 65 Hz  Frequency
In / 5 A Nominal current
1,1 In Permanent overload
 0,75 VA Current circuit consumption
Transistor output features
NPN Type: Opto.isolated transistor (open collector)
24  V dc Maximun operating voltage
50 mA Maximun operating current
5 pulses/sec. Maximun frequency
100 ms Lenght of pulse
RS 485 Communication
Cat. III – 300 V ca / 520 ca   EN-61010  Safety
Class II double insulation against electric shock
IEC 61000 Standards:    
IEC 61000-4-3
IEC 61000-4-4
IEC 610004-5
IEC 610004-11
EN 61000-6-1 
EN 61000-6-3
EN-61010-1
VDE 0110
UL 94 
Voltage (V) Communication Module Dimensions
(mm)
Model Part Number

85 … 265 Vac

95 … 300 Vcc

YES  96 x 96 New MCA Plus Advanced MCAPLUSII