Description

LIFASA automatic capacitor banks are used for centralized compensation of power factor in low voltage installations.

These equipments are supplied completely assembled and ready for use: it is only necessary to connect it to the mains with cables of adequate cross section, and to supply the operation signal from a suitable current transformer.

General characteristics
LIFASA automatic capacitor banks are composed of the following elements:

• High rupturing capacity (HRC) fuses connected to a busbar system.
• Contactors specially adapted to the work with capacitors.
• Inrush current limiting inductances.
• Fast discharge resistors.
• Low losses power capacitors.
• Reactive power controllers.
• Terminals for neutral and ground conductors.
• Metal cabinet containing all the switchgear.

Advantages
• Equipments wired and tested at works, full finished and supplied with all control and safety devices.

• Easy transportation and installation due to their light weigh.

• Easy selection of the most appropriate cos φ to avoid penalty charges on tariffs.

• Long life and high reliability, thank to the use of self-healing and low losses capacitors.

• Wide range of power (from 5 to 1600 kvar, 440 V) with standard equipments for immediate delivery.

• Option of including various accessories.

Special equipment
On request, automatic capacitor banks can be produced to customers special requirements. Among the different possibilities are the following:
• Other voltages and frequencies.
• Capacitor banks with different degrees of protection.
• Capacitor banks for outdoor installation.
• Working program 1:2:4:4:, 1:2:4:8:,1:1:2:2:.
• Fixed step (for transformer compensation).
• Higher powers than the above stated.

Technical characteristics
230 / 440 /690 V Rated voltage
50 Hz – 60 Hz Rated frequency
5 … 1600 kvar Rated power
< 0.2 W/kvar Dielectric losses
< 0.5 W/kvar Capacitors losses
1.1 Un (8h/day) Maximum overvoltage
1.3 In Maximum overcurrent
On each contactor Fast discharge resistors
MCE ADV or Master controller Regulation equipment
1:1:1:1 / 1:2:2:2 / 1:2:4:4 /1:2:4:8 / 1:1:2:2 /… Working programs
230 V Control voltage
… /5 (Optional) External current transformer
-25ºC/+45 ºC max. temp. Temperature range
IP 21 Degree of protection
Indoor Installation
IEC 60831 Standars
IEC 60439
EN 60439-1
EN 60831