Description

INAS/INRS reactors are designed to work in supply systems with a high level of harmonic distortion and static contactors in such a way that they allow a safe and reliable service of the power factor correction equipments. Reactors are connected in series with static contactor and power capacitors, forming a resonant circuit conveniently detuned, so that, the whole unit has an inductive impedance at the frequencies of all harmonics present in the installation. These reactors are specially designed to work in series with FMLFS capacitors.

Technical characteristics
230 /400V Rated voltage of mains 
50 Hz – 60 Hz Rated frequency
260/460 V Rated voltage of capacitors
Low tuning Filter type
189 Hz (7%) Resonance frequency
±3% Inductive tolerance
0.35 In  Max. harmonics overload
INAS: Aluminum Construction
INRS: Copper
By termostat Thermal protection
2 kV Insulation level
Terminal block Connection
INAS: IP 00/INRS: IP20 Degree of protection
Indoor Installation
IEC 60289 Standards
EN 60289

Other powers, tensions and frequencies to consult

Capacitor code Weight (kg) Losses (W) Dimensions (mm) Filter Code
      d w h Un  (V) Qn  (Kvar)  
FMLFS4606 6 25 92 155 165 400 5 INRS40057
FMLFS4612 8 50 102 180 190 400 10 INRS40107
FMLFS4618 9,5 57 112 180 190 400 15 INRS40157
FMLFS4625 11,5 76 122 180 190 400 20 INRS40207
FMLFS4631 17 90 122 240 250 400 25 INRS40257
FMLFS4637 20,5 120 132 240 250 400 30 INRS40307
FMLFS4649 25,5 145 147 240 250 400 40 INAS40407
FMLFS4661 29 185 154 310 233 400 50 INAS40507
FMLFS4674 30 205 154 310 234 400 60 INAS40607
FMLFS4698 41 235 165 338 280 400 80 INAS40807