Description
CPM series are formed by connecting a FML capacitor to an automatic circuit breaker.
Its construction facilitates connection of the capacitor in installations where individual compensation of motors and transformers is required. It offers secure protection against transients and permanent overloads.
Technical characteristics | |
230/440 V | Rated voltage |
50 Hz – 60 Hz | Frecuency |
3 kV rms/15kV crest | Insulation level |
1.1 Un (8h/day) | Max. overvoltage |
1.3 In | Max. overcurrent |
-40/+55 ºC | Temperature range |
Indoor | Installation |
≤125 A (MCB): 10 kA | Breaking capacity in at 415V |
>125 A (MCCB): 50 kA | |
RAL7035 | Colour |
IEC 60831 | Standards for capacitors |
EN 60831 |
Other constructions, powers, tensions and frequencies to consult.
Weight (kg) | h (mm) | In (A) | Un (V) | Qn (kvar) | Interruptor (A) | Part number |
7 | 270 | 7.2 | 440 | 5 | 16 | CPM4405 |
8 | 270 | 10.8 | 440 | 7.5 | 20 | CPM4407 |
8 | 270 | 14.4 | 440 | 10 | 25 | CPM4410 |
9 | 270 | 21.7 | 440 | 15 | 32 | CPM4415 |
10 | 270 | 28.9 | 440 | 20 | 40 | CPM4420 |
10 | 270 | 36.1 | 440 | 25 | 50 | CPM4425 |
11 | 270 | 43.3 | 440 | 30 | 63 | CPM4430 |
12 | 270 | 57.7 | 440 | 40 | 80 | CPM4440 |
16 | 270 | 72.2 | 440 | 50 | 100 | CPM4450 |
18 | 460 | 86.6 | 440 | 60 | 125 | CPM4460 |
20 | 460 | 108.3 | 440 | 75 | 160 | CPM4475 |
22 | 460 | 115.5 | 440 | 80 | 160 | CPM4480 |
9 | 270 | 12.5 | 230 | 5 | 25 | CPM2305 |
10 | 270 | 18.8 | 230 | 7.5 | 32 | CPM2307 |
10 | 270 | 25.1 | 230 | 10 | 40 | CPM2310 |
11 | 270 | 37.7 | 230 | 15 | 50 | CPM2315 |
16 | 270 | 50.2 | 230 | 20 | 80 | CPM2320 |
17 | 270 | 62.8 | 230 | 25 | 100 | CPM2325 |
18 | 270 | 75.3 | 230 | 30 | 100 | CPM2330 |
20 | 460 | 100.4 | 230 | 40 | 160 | CPM2340 |