Description

In installations with 3rd harmonic generation loads, the current through the neutral cable can be higher than the one in the phases, even in case of balanced loads. The most proper solution for these problems is to use a specific equipment for the 3rd harmonic filtering, consisting basically in a three-phase isolating transformer, delta-star connected, that completely eliminates the 3rd harmonic current, plus a passive filter which reduces the 5th harmonic.

Technical characteristics
Isolating transformer
3×400 V Rated voltage of the primary
3×230 V Rated voltage of the secondary
50 Hz Frequency
Delta Primary connection
Star Secondary connection
Copper Wiring
Protections
6A bipolar circuit breaker Control circuit
Three-phase earth leakage switch (30mA to 300mA) Power circuit
-10/+40ºC Climatic range
IP42 Protection
Weight (kg) Dimensions (mm) Un (V) Power (kVA) Part Number
  H A L      
125 800 500 590 3X400/230 10 TFA-40010
160 800 500 590 3X400/230 15 TFA-40015
185 800 500 590 3X400/230 20 TFA-40020
265 1050 750 900 3X400/230 30 TFA-40030
325 1050 750 900 3X400/230 40 TFA-40040
350 1050 750 900 3X400/230 50 TFA-40050
420 1050 750 900 3X400/230 80 TFA-40080
470 1050 750 900 3X400/230 100 TFA-40100